Product demand and challenges
1 , automation features
Automatic start and automatic loading
Or remote -controlled unit received a start command automatically, the startup success rate greater than 99 %. A boot loop including three starts, intermittent time between two starts for 10-15 seconds ;
After the success of the unit starts when oil pressure reaches a predetermined value should be able to automatically load , load time is usually 10 seconds ; Three starts after the failure of the unit no longer start , and issue an alarm signal fails to start , if the standby unit should be able to start the command passed to the standby unit .
Automatic unloading shutdown
After the unit has received a stop command or remote -controlled , automatic unloading stop, its shutdown mode has two normal shutdown and emergency shutdown . Normal shutdown procedure : After cutting off the main circuit ( ATS off air switch or switch to mains side ) ; emergency shutdown procedure : immediately cut off the main circuit , fuel oil line .
Automatic protection unit has low oil pressure , over- voltage , over speed, overload, short circuit, phase protection, water-cooled units with high temperature protection, air-cooled units with high cylinder temperature protection.
2, the remote monitoring function
Meet the technical requirements of remote monitoring with telemetry and remote control functions, real-time remote monitoring of operating parameters of the unit, running, when the unit is abnormal conditions or serious faults can automatically alert the monitoring center, and can achieve remote control unit . Able to provide standard communication protocols.
3, string, and machine function
String Machine backup function: can be used with ATS dual standby switching function automatically switches between electricity and diesel generator set or two diesel generators.
And machine expansion features: two or more specifications identical three-phase units, at rated power factor, to meet the (20-100)% of rated power stability within the scope of the parallel run. In order to improve the active and reactive power accuracy and stability of the rational allocation run, requiring diesel unit in the steady-state speed droop governor has within (2-5)% range adjustment device. In the control box (screen) in the steady-state voltage regulator allows the device to adjust the rate of adjustment in the range of 5%.
4, working conditions
Altitude can run 3000 meters;
Ambient temperature limit is -15 C °, the upper limit is 40 C °, can choose other environmental unit.
5, stable performance, high reliability
MTBF of units is not less than 2000 hours.
6, easy refueling facilities and protective measures
The unit has an external fuel system and is equipped with a lock function;
Usually requires large fuel tank, which can meet 12-24 hours to run.

Solutions
Excellent performance and stable generators, low noise design, equipped with PLC-5220 control system with AMF function, ATS connection through and ensure Telegraph once stood in the main power off, the system must be able to provide alternative power supply immediately.

Superiority
Complete set of products, programs, and reduce the technical mastery required to make the unit easier to use and easier to maintain;
· Control system with AMF function, automatic start and automatic shutdown and alarm functions under a number of monitoring;
· Optional ATS, a small unit can be used built-in unit ATS;
· Ultra-low noise generation, 30KVA units below the noise level of 7 meters 60dB (A) or less;
· Stable performance, MTBF of units is not less than 2000 hours;
· Small units, matching some of the device in cold areas and high temperatures to achieve regional operational requirements;
· The special needs of some customers can be custom designed and developed.